How much solar does a new NYC building need? (sizing table)

How much solar does a new NYC building need? (sizing table)

Updated · R Solar Solutions

Quick answer: Under the 2025 NYC Energy Code (Section C405.15), a new building covered by the commercial chapter needs on-site solar capacity of 0.75 W DC per square foot of gross conditioned floor area, counting up to the three largest floors. So a building with three 10,000 sq ft floors needs about 22.5 kW; with 5,000 sq ft floors, about 11.3 kW. Buildings under 5,000 sq ft total are exempt.

Questions? Call Jack at (646) 535-8762

Serving Brooklyn, Manhattan, Queens, The Bronx, Staten Island, Long Island and Westchester.

Sizing table for typical NYC floor plates (three largest floors equal)

2,500 sq ft floors: 5.6 kW (about 13 panels, ~390 sq ft of roof)

4,000 sq ft floors: 9.0 kW (about 21 panels, ~630 sq ft of roof)

6,000 sq ft floors: 13.5 kW (about 32 panels, ~940 sq ft of roof)

8,000 sq ft floors: 18.0 kW (about 43 panels, ~1,260 sq ft of roof)

10,000 sq ft floors: 22.5 kW (about 54 panels, ~1,580 sq ft of roof)

15,000 sq ft floors: 33.8 kW (about 80 panels, ~2,360 sq ft of roof)

20,000 sq ft floors: 45.0 kW (about 107 panels, ~3,150 sq ft of roof)

Will it fit on the roof?

A rough rule is 60–80 sq ft of clear flat roof per kW. On a tall, narrow building the requirement grows with floor area but the roof doesn't, while setbacks, bulkheads and mechanicals take roof space — so many mid-rise buildings fit most but not all of the requirement. The shortfall can be met with off-site renewable energy, as the code allows. A roof layout at schematic design tells you early.

Why the three largest floors

The code caps the floor area used in the formula at the three largest floors, so a 12-story building with equal floor plates needs the same capacity as a 3-story one with the same plates. That keeps the requirement roughly in line with what a roof can hold.

Common questions

Is the 0.75 W per square foot AC or DC?

It is DC nameplate capacity of the on-site renewable system.

Does a 2-story building need solar?

If it is under the commercial chapter and has 5,000 sq ft or more of conditioned floor area, yes, using all floors (fewer than three). Under 5,000 sq ft it is exempt from C405.15; LL92/94 may still apply.

How do I get an exact number?

Send us the floor areas or the drawings. We return the required kW, a roof layout and a price.

Questions? Call Jack at (646) 535-8762

Serving Brooklyn, Manhattan, Queens, The Bronx, Staten Island, Long Island and Westchester.

Sources: NYC DOB: 2025 NYCECC Chapter C4 (C405.15) · NYC DOB: 2025 NYCECC lighting & power guide · NYC DOB: 2025 NYCECC enforcement notice

This page is general information, not tax, legal or engineering advice. Incentives change — confirm eligibility with your tax advisor. R Solar Solutions is operated by P National Group LLC, 1 Northside Piers, Brooklyn, NY 11249. Incentive information is general and not tax advice.

Related

Call Jack nowFree quote